U01b - Fume Hood Hibernation-Un-Hibernation
PURPOSE:
Service Requests for Fume Hood Hibernation/Un‐Hibernation. Verify correct information on a SR so the zone can efficiently prioritize the work.
STEPS NEEDED:
-
Service Request for Fume Hood Hibernation
While following SOP U1 or U2, verify the following information is provided on the SR:
- Summary: Hibernate hood [with identification code]
- Long Description:
- An estimate of how long the fume hood will be hibernated.
- Contact information of the requestor (if the requestor information is not already displayed in the Requestor fields of the SR) should be here as well.
- Additional information as needed.
- Classification: Repair, Maintenance, Service
- Priority: 30
- Service: HVACR
- Crew: CONTROL
- GL Account: IT‐R614705‐?????‐6470‐???‐??????????‐000147
- Important: Please verify the hood has been emptied of all contents prior to sending the SR to the zone.
-
Service Request for a Fume Hood Un‐Hibernation
- Summary: Un‐hibernate hood [with identification code]
- Long Description:
- Contact information of the requestor (if the requestor information is not already displayed in the Requestor fields of the SR) should be here as well.
- Additional information as needed.
- Classification: Repair, Maintenance, Service
- Priority: 40
- Service: HVACR
- Crew: CONTROL
- GL Account: IT‐R614705‐?????‐6470‐???‐??????????‐000147
- Target Finish Date: 48 hours after SR reported date*
* There is a policy that hoods will be turned back on within 48 hours of SR submission.
RESULTS:
Appropriate information will be provided on a Maximo service request for a fume hood hibernation or un‐hibernation service request before sending the SR to the zone. For a hibernation requests, hood will be emptied of all contents prior to sending the SR to the zone.