Utility Shutdown Request 40562
Request Status
Request Number
40562
Emergency Request
No
Requestor's Name
Michael Dempsey
Requestor's Email
mfd26@cornell.edu
Requestor's Phone
607-327-1820
Department/Company
Control Shop
Request Start Date/Time
Request End Date/Time
Systems Affected
Building Chilled Water System
Areas Affected
Entire Building
Comments
Need to shut down building chilled water system for one hour to test by-pass check valve, which could be the cause of high CW supply temperature and low DP pressure on the campus loop. Will do this shut down first thing in the morning, all researchers should be aware that there will be no cooling for one hour.
EHS Request
No
EHS Reason for Shutdown
Check By-Pass Check Valve On Building CW System For Failure.
Work Order Numbers
175221820
Notification Comments
unable to reach tom by phone, sent an email to confirm utility shut down is ok
Tom Quin approved of shut down via email.
07/10/2025 UPDTAE
Domonique -
As of now, there has been no pushback. I’ll wait one more day and confirm tomorrow.
Best,
Seetha
________________________________________
07/11/2025 Domonique -
I haven’t received any pushback from the labs in Snee, so we’re good to go. Have a great weekend!
Best,
Seetha
________________________________________
Tom Quin approved of shut down via email.
07/10/2025 UPDTAE
Domonique -
As of now, there has been no pushback. I’ll wait one more day and confirm tomorrow.
Best,
Seetha
________________________________________
07/11/2025 Domonique -
I haven’t received any pushback from the labs in Snee, so we’re good to go. Have a great weekend!
Best,
Seetha
________________________________________
Assignment History
<ul><li>Requested by Michael Dempsey - 07-08-2025 12:41PM</li><li>Submitted by mfd26 - 07-08-2025 12:41PM</li><li>Email notification is sent by mfd26 - 07-08-2025 12:41PM to: fcscrequest@cornell.edu,mfd26@cornell.edu</li><li>Assigned to dnm64 by dnm64 - 07-08-2025 2:56PM</li><li>Status changed to Assigned by dnm64 - 07-08-2025 2:56PM</li><li>Email notification is sent by dnm64 - 07-08-2025 2:56PM to: dnm64@cornell.edu</li><li>Record updated by dnm64 - 07-09-2025 12:08PM</li><li>Status changed to Pending Approval by dnm64 - 07-09-2025 12:39PM</li><li>Email notification is sent by dnm64 - 07-09-2025 12:39PM to: fcscrequest@cornell.edu,ls249@cornell.edu,jrs579@cornell.edu,kmn64@cornell.edu,jo422@cornell.edu,eas454@cornell.edu,plw6@cornell.edu,dnm64@cornell.edu,rg833@cornell.edu</li><li>Approved by eas454 - 07-09-2025 3:35PM</li><li>Status changed to Scheduled by eas454 - 07-09-2025 3:35PM</li><li>Email notification is sent by eas454 - 07-09-2025 3:35PM to: fcscrequest@cornell.edu,fcs-shutdown-l@cornell.edu,mfd26@cornell.edu,sv476@cornell.edu,tlq3@cornell.edu</li><li>Record updated by dnm64 - 07-10-2025 2:43PM</li><li>Record updated by dnm64 - 07-14-2025 1:49PM</li></ul>
Terms & Conditions
Yes
Affected Facility
Notify People
fac-2049: Seetharaman Vinayagam; sv476@cornell.edu; 607-255-8967; level-1
fac-2049: Thom Quinn; tlq3@cornell.edu; +1 (607) 2553540; level-2
Assignee
Approver
EHS City Tie
On
EHS Horns
On
EHS Zones
On
EHS Devices
On
EHS SRB
On
EHS Relays
On
EHS Spare
On
EHS PIVA
On
EHS Ground Values
On
EHS Drains Open
On
EHS Air Control
On
EHS Jockey Pump
On
EHS Fire Pump
On
EHS Control Values
On
EHS Other
On
EHS Loops
On