Utility Shutdown Request 35573
Request Status
Request Number
35573
Emergency Request
No
Requestor's Name
Jon Minarski
Requestor's Email
jdm444@cornell.edu
Requestor's Phone
607-882-5801
Department/Company
Engineering & Project Management
Request Start Date/Time
Request End Date/Time
Request Shop Assistance
Systems Affected
ATS that feeds panel HEDP-LR-SB01.
Areas Affected
Elevators, Fans SPF-3, PF-1, SPF-1, SPF-2, and SPF-4.
Comments
ATS feeds panel HEDP-LR-SB01 which has a 100amp breaker, a 225amp breaker, and a 15amp breaker in it. The 15A breaker feeds a drive for fan SPF-3. The 225A feeds a transformer which feeds the elevators. The 100A feeds panel HEP-LR-R01 on the roof which feeds drives for fans PF-1, SPF-1, SPF-2, and SPF-4.
Davies Orinda has been in touch with electrical shop group and they are aware this is coming.
Davies Orinda has been in touch with electrical shop group and they are aware this is coming.
EHS Request
No
EHS Reason for Shutdown
To rectify the issue where the elevators stop functioning anytime the generators are running.
Work Order Numbers
15640456
Notification Comments
Greg.S Approved shutdown 8/4/23
Archie.R Approved shutdown 8/4/23
CS Added Kevin.S For notification
Archie.R Approved shutdown 8/4/23
CS Added Kevin.S For notification
Assignment History
<ul><li>Requested by Jon Minarski - 08-04-2023 08:40AM</li><li>Submitted by Jon Minarski - 08-04-2023 08:40AM</li><li>Email notification is sent by Jon Minarski - 08-04-2023 8:40AM to: fcscrequest@cornell.edu,jdm444@cornell.edu</li><li>Assigned to Emily Ann Sickmon by Emily Ann Sickmon - 08-04-2023 8:42AM</li><li>Status changed to Assigned by Emily Ann Sickmon - 08-04-2023 8:42AM</li><li>Email notification is sent by Emily Ann Sickmon - 08-04-2023 8:42AM to: eas454@cornell.edu</li><li>Status changed to Pending Approval by Emily Ann Sickmon - 08-04-2023 9:34AM</li><li>Email notification is sent by Emily Ann Sickmon - 08-04-2023 9:34AM to: fcscrequest@cornell.edu,ls249@cornell.edu,jrs579@cornell.edu,kmn64@cornell.edu,eas454@cornell.edu</li><li>Approved by Kara M Nash - 08-04-2023 9:38AM</li><li>Status changed to Scheduled by Kara M Nash - 08-04-2023 9:38AM</li><li>Email notification is sent by Kara M Nash - 08-04-2023 9:38AM to: fcscrequest@cornell.edu,fcs-shutdown-l@cornell.edu,jdm444@cornell.edu,gjs25@cornell.edu,ajr334@cornell.edu,kcs33@cornell.edu </li><li>Record updated by Emily Ann Sickmon - 08-04-2023 11:39AM</li><li>Email notification is sent by Emily Ann Sickmon - 08-04-2023 11:40AM to: fcscrequest@cornell.edu,fcs-shutdown-l@cornell.edu,jdm444@cornell.edu,gjs25@cornell.edu,ajr334@cornell.edu,kcs33@cornell.edu </li></ul>
Terms & Conditions
Yes
Affected Facility
Notify People
fac-1028B: Gregory Smith; gjs25@cornell.edu; +1 (607) 229-0219; level-1
Archie Resue; ajr334@cornell.edu; 607-239-0230
Kevin Samson ; kcs33@cornell.edu ; 607-592-6244
Assignee
Approver
EHS City Tie
On
EHS Horns
On
EHS Zones
On
EHS Devices
On
EHS SRB
On
EHS Relays
On
EHS Spare
On
EHS PIVA
On
EHS Ground Values
On
EHS Drains Open
On
EHS Air Control
On
EHS Jockey Pump
On
EHS Fire Pump
On
EHS Control Values
On
EHS Other
On
EHS Loops
On