Utility Shutdown Request 39194

Submitted by ajp327 on
Request Status
Request Number
39194
Emergency Request
No
Requestor's Name
Jake Perno
Requestor's Email
ajp327@cornell.edu
Requestor's Phone
6076613194
Department/Company
FCS Engineering and Project Management
Request Start Date/Time
Request End Date/Time
Systems Affected
Power
Areas Affected
Entire building
Comments
8pm-12 am- Tie in normal feed from main gear to ATS
Turn Off breakers :
-DP-5ACI
-MCC-P1
12am restore power to all main switchgear breakers.
12am-2 am Tie EM feed From disconnect to Generator set
Lock generator out so it wont start ( no effect unless nature causes power outage)
If normal power is lost at this point everything will be made safe and restore generator
EM power ASAP
2 am - 3am Disconnect old Elevator Feed to prep for new feed
Elevators will be out of service at this time
Isolate panel DS-EM
Feeders out of DS-EM
-DP-EL
-DP TEL
-MCC-GEM
-DP-PEM
-ELP-1
-ELP- 4
-LP-P
- RS-1 ( ACS-6)
- (Safety)
While this panel is down the new breaker for BA #4 will be installed into panel DP-TEL
3am Restore power to DS-EM
3am - 4am Tie old elevator feed into new ATS switch
Elevators will still be out of service during this process
4am Turn elevators on with completion of shutdown
EHS Request
No
EHS Reason for Shutdown
Install new ATS for elevators
Notification Comments
Seetha aware of shut down & Steph
Assignment History
<ul><li>Requested by Jake Perno - 02-11-2025 10:57AM</li><li>Submitted by ajp327 - 02-11-2025 10:57AM</li><li>Email notification is sent by ajp327 - 02-11-2025 10:57AM to: fcscrequest@cornell.edu,ajp327@cornell.edu</li><li>Assigned to dnm64 by dnm64 - 02-11-2025 11:00AM</li><li>Status changed to Assigned by dnm64 - 02-11-2025 11:00AM</li><li>Email notification is sent by dnm64 - 02-11-2025 11:00AM to: dnm64@cornell.edu</li><li>Status changed to Pending Approval by dnm64 - 02-12-2025 9:09AM</li><li>Email notification is sent by dnm64 - 02-12-2025 9:09AM to: fcscrequest@cornell.edu,ls249@cornell.edu,jrs579@cornell.edu,kmn64@cornell.edu,jo422@cornell.edu,eas454@cornell.edu,ap756@cornell.edu,dnm64@cornell.edu,rg833@cornell.edu</li><li>Record updated by kmn64 - 02-12-2025 9:45AM</li><li>Approved by kmn64 - 02-12-2025 9:45AM</li><li>Status changed to Scheduled by kmn64 - 02-12-2025 9:45AM</li><li>Email notification is sent by kmn64 - 02-12-2025 9:45AM to: fcscrequest@cornell.edu,fcs-shutdown-l@cornell.edu,ajp327@cornell.edu,sv476@cornell.edu,sam265@cornell.edu,tdb26@cornell.edu</li></ul>
Terms & Conditions
Yes
Affected Facility
Notify People
fac-2051: Seetharaman Vinayagam; sv476@cornell.edu; 607-255-8967; level-1
fac-2051: Stephanie Pierson; sam265@cornell.edu; +1 (607) 2557767; level-2
fac-2051: Tom Ball; tdb26@cornell.edu; +1 (607) 2556518; level-3-CIT Equipment (Elec/HVAC)
Assignee
Approver
EHS City Tie
On
EHS Horns
On
EHS Zones
On
EHS Devices
On
EHS SRB
On
EHS Relays
On
EHS Spare
On
EHS PIVA
On
EHS Ground Values
On
EHS Drains Open
On
EHS Air Control
On
EHS Jockey Pump
On
EHS Fire Pump
On
EHS Control Values
On
EHS Other
On
EHS Loops
On